1.1.3.6 Handrails
General guidance on handrails and guarding is given in TGD K, but
the guidance that follows applies to handrails on accessible access
routes.
Where handrails are provided on a ramped or stepped access
route:
(a)
The vertical height to the top of the upper
handrail from the pitch line of the surface of a flight should be
between 900mm and 1000mm and from the surface of a landing
should be between 900mm and 1100mm (refer to Diagram 6).
Where a second handrail on stairs is provided for children or those
of short stature the vertical height to the top of a second lower
handrail from the pitch line of the surface of a flight should be
between 600mm and 700mm;
(b)
Where there are two or more flights separated by a landing or
landings, the handrails should be continuous across flights and
landings, except where broken by side access routes on landings;
(c)
Where the handrail is not continuous the handrail should extend
at least 300mm beyond the top and bottom of a ramped approach
and the top and bottom risers of a stepped approach, and
terminate in a closed end which does not project into a route of
travel. Handrails should be
terminated in such a way that reduces the risk of clothing being
caught;
(d)
The background against which the handrails are seen should
contrast visually without being highly reflective (refer to 1.6.4);
(e)
The profile should be either circular with a diameter of between
40mm to 50mm or oval with a width of 50mm (refer to Diagram 7);
(f)
Handrails should not protrude more than 100mm into the surface
width of the access route where this would impinge on the stair
width requirement of TGD B – Methods of Measurement;
(g)
There should be a clearance of at least 50mm to 60mm between
the handrail and any adjacent wall surface (refer to Diagram 7);
(h)
There should be a clearance of at least 50mm between a cranked
support and the underside of the handrail (refer to Diagram 7). The
handrail support should meet the handrail centrally on its
underside. Rationale: This will minimise the risk of the handrail
supports interrupting the smooth running of a person’s hand along
the rail;
(i)
The handrails inner face should be located no more than 50mm
beyond the surface width of the access route (refer to Diagram 7);
(j)
Handrail fixings should be designed to meet the loading
recomendations of I.S. EN
1991-1-1:2002.
Extract from Building Regulations Part K and Part M;